BTU Flowmeter IEFB-GN-10-R10-COM-LCD

BTU Flowmeter IEFB-GN-10-R10-COM-LCD

IEFB-SN-10-R10-COM.2

BTU Flowmeter IEFB-GN-10-R10-COM-LCD

Source of Supply: Directly imported by DLK TRADING SERVICE COMPANY LIMITED ⭐⭐⭐⭐⭐ Product Line: IEFB-GN-10-R10-COM-LCD✅ Certifications: 💨 For Use: Chất Lỏng⚙️ Product Type: Cảm Biến🔧 Functions: Giám sát lưu lượng

Product information

The Dwyer Series IEFB is an insertion thermal energy meter that combines flow measurement, temperature measurement and energy calculation in a single device. Model IEFB-GN-10-R10-COM-LCD is configured for pipe sizes greater than 10 to 36 inches (250–900 mm), with a 1" male NPT process connection, 10 ft PT temperature sensors with hot-tap thermowells, BACnet MS/TP or Modbus® RTU communication and an integral LCD display.

✔ Suitable measurement accuracy: The G configuration provides ±1% FS standard accuracy for pipe sizes greater than 10 to 36 inches (250–900 mm)
✔ Flow and energy measurement: Integrates a flow sensor, two PT temperature sensors and an energy calculator into a single device
✔ Flexible BMS communication: Supports BACnet MS/TP or Modbus® RTU over 2-wire RS-485, with protocol selection available from the display
✔ Integral LCD display: 2 x 2 inch (50 x 50 mm) graphic LCD provides clear readings and allows device configuration from the display
✔ Integrated temperature sensing: The R10 configuration includes two 10 ft (3 m) PT temperature sensors with hot-tap thermowells for supply and return temperature measurement
✔ No moving parts: Electromagnetic technology minimizes mechanical components that can wear, while the electrodes are designed to discourage fouling
✔ HVAC and energy management applications: Suitable for monitoring chiller performance, boilers, chilled water, condenser water, heating water and energy cost allocation

 

Tags:
  • 🚚 Direct Importer by  DLK TRADING SERVICE COMPANY LIMITED .
  • ✅ Quality :  100% Brand New , genuine products with complete import documentation.
  • 🛠️ Warranty :  12 Months (optional 36 Months ).
  • 📞 Phone  :  0937972339

Technical Specifications

Model IEFB-GN-10-R10-COM-LCD
Device Type Insertion Thermal Energy Meter
Service Compatible clean or dirty non-coating, conductive liquids
Velocity Range 0 to 20 ft/s (0 to 6 m/s)
Flow Sensor Accuracy ±1% FS
Temperature Accuracy Class B, ±(0.30 + 0.005×t)°C per EN60751
Thermal Energy Accuracy Class 3 at 6.5 to 20 ft/s (2 to 6 m/s)
Pipe Size >10 to 36" (250 to 900 mm)
Process Connection 1" Male NPT
Temperature Sensors Two PT temperature sensors, 10 ft (3 m) cables, with hot-tap thermowells
Electrical Connection PG16 gland with two 10 ft (3 m) cables, 9-conductor, 22 AWG
Communication Protocol BACnet MS/TP or Modbus® RTU, display selectable
Communication Interface 2-wire RS-485
Baud Rates 9600 / 19200 / 38400 / 57600 / 76800 / 115200 bps
Analog Output 4-20 mA, 0-5 V, 0-10 V or 2-10 V, display selectable
Pulse / Frequency Output 0-15 V peak pulse, 0-500 Hz or scalable pulse output
Alarm Outputs Two alarms for empty pipe detection or minimum/maximum velocity; reverse flow output indication
Display 2 x 2" (50 x 50 mm) graphic LCD with backlight
Ambient Temperature Limit -20 to 160°F (-29 to 71°C)
LCD Temperature Limit -4 to 158°F (-20 to 70°C)
Process Temperature Limit 15 to 250°F (-9 to 121°C)
Pressure Limit 400 psi (27.6 bar) @ 100°F (37.8°C)
Wetted Materials Body shaft/fitting: 316 SS; electrodes: 316 SS; electrode cap: polymer/polystyrene; O-ring: silicone; thermowells: 304 SS
Power Requirements 12-42 VDC, 0.25 A @ 24 VDC; 12-36 VAC
Conductivity >20 µS/cm
Enclosure Rating NEMA 4X (IP66) – LCD version
Enclosure Material Powder-coated die-cast aluminum
Straight Run Requirements >10 upstream, >5 downstream
Pressure Drop <0.1 psi at 12 ft/s in 4" and larger pipe
Relative Humidity 10 to 90% non-condensing
Compliance BTL
SERIES IEFB - SERIES A-IEF INSERTION TYPE ELECTROMAGNETIC FLOW TRANSMITTER, INSERTION TYPE FLOW SENSOR, FLOW MEASURING DEVICE, REMOTE DISPLAY FOR IEF AND IEFB SERIES
Specification Description
Service Compatible clean or dirty non-coating, conductive liquids
Range 0 to 20 ft/s (0 to 6 m/s). For max flowrates >10 ft/s (3 m/s) order option -CC
Wetted Materials Body shaft/fitting: 316 SS; Electrodes: 316 SS; Electrode cap: Polymer/polystyrene; O-ring: Silicone; Thermowells: 304 SS
BTU Accuracy High Accuracy Units: Class 2 (2 to 20 ft/s); Standard Accuracy Units: Class 3 (6.5 to 20 ft/s)
Flow Sensor Accuracy High Accuracy Units: ±0.5% of reading, ±1% (2 to 20 ft/s); Standard Accuracy Units: ±1% FS
Temperature Accuracy Class B ±(0.30 + 0.005*t)°C per EN60751
Differential Temperature Accuracy Et = ±[0.5 +3*(Delta)(Theta)min/(Delta)(Theta)] %
Calculator Accuracy Ec = ±[0.5 +(Delta)(Theta)min/(Delta)(Theta)] %
Temperature Compensation 140 to 220°F, < 2% error over ±30°F; 40 to 70°F, < 2% error over ±10°F
Temperature Limits Ambient: -20 to 160°F; Process: 15 to 250°F; Storage: -40 to 185°F
Process Connection Flowmeter: 1" NPT or BSPT; Thermowell: (2) 1/2" NPT or BSPT
Pressure Limit 400 psi (27.6 bar) @ 100°F
Pressure Drop < 0.1 psi at 12 ft/s in 4" pipe
Outputs Analog, Pulse/Frequency, Alarm
Power Requirements 12-42 VDC, 12-36 VAC
Electrical Connection Removable terminal blocks, multiple conduit options
Display 2 x 2" graphic LCD with backlight
Conductivity >20 microsiemens
Enclosure Material Powder coated die cast aluminum
Enclosure Ratings NEMA 6P (IP68) or NEMA 4X (IP66)
Agency Approvals BTL
Communication Options BACnet MS/TP or Modbus RTU
Applicable Pipe Material Carbon steel, SS, copper, UPVC, PVDF, etc.
Applicable Pipe Size 4 to 36" (100 to 900 mm)
Diameter Length Requirements >10 upstream, >5 downstream
Relative Humidity 10 to 90% non-condensing
Output Impedance 4 to 20 mA: 536 Ω; 10V: 1.27k Ω

 

IEFB_CATALOG_DWYER_DLK.pdf
IEFB_DATASHEET_DWYER_DLK.pdf
IEFB_MANUAL_DWYER_DLK_1
IEFB_MANUAL_DWYER_DLK_2
APPROVAL 1
APPROVAL 2

 

 

Mã SP:IEFB-GN-10-R10-COM-LCD

Quy cách:

Tình trạng:

Price: