NCT NA02AA Alkali Leak Detection Kit | DLK Vietnam

NCT NA02AA Alkali Leak Detection Kit | DLK Vietnam

nb01aa - nct

NA02AA

NCT NA02AA Alkali Leak Detection Kit | DLK Vietnam

Product information

The NCT Alkali Leak Detection Kit detects NaOH, KOH, NH₃, H₂O₂… leaks within 1 second, from below 0.5 mL; the NA02AA cable reacts selectively and tells chemicals from water – for caustic dosing, wastewater treatment, tanks and semiconductor fabs.

The kit includes NA02AA cable (per metre), the NB01AA controller (2 zones, Form C relays, RS-485 Modbus) and NC01AA connectors; connects to BMS/DCS or the ND01AA alarm panel. Genuine products supplied by DLK Trading Service Company Limited – NCT's authorized strategic partner in Vietnam.

Tags:
  • 🚚 Direct Importer by  DLK TRADING SERVICE COMPANY LIMITED .
  • ✅ Quality :  100% Brand New , genuine products with complete import documentation.
  • 🛠️ Warranty :  12 Months (optional 36 Months ).
  • 📞 Phone  :  0937972339

What is included in the solution?

The NB01AA controller shows real-time values, allows sensitivity tuning per sensor type and site, provides 2 Form C relays for interlocks (pump stop, valve close, beacon) and transmits data via RS-485 Modbus to BMS/SCADA/DCS; optional IoT LoRa sends alerts to phones for unmanned areas.

Component Code Function Quantity rule Type
Alkali leak sensor cable NA02AA Selective response to alkali chemicals Per metre – per zone length Required
2-channel chemical sensor controller NB01AA Display, alarm, Form C relays, RS-485 Modbus, IoT LoRa 1 per 2 zones Required
Chemical sensor connector NC01AA Connects the film to the controller 2 per zone (both ends) Required
24 VDC power supply SMPS 24VDC Powers the controllers, DIN-rail in panel ≥ 24 VDC / 1 A (per NCT); size up for multiple controllers Required
Master controller NB02AA Central management of up to 30 NB01AA via RS-485 When many NB01AA units are used Optional
Corner / flexible link NC02AA / NC06A Turns and crossings – chemical-sensor compatible Per route Optional
PVC sensor case (recommended for highly corrosive chemicals) NF02A-C Protects film where metal is not allowed Per section (200–2,000 mm) Optional
SUS sensor case NF01A-C Outdoor and mechanical protection Per section Optional
Connector case / cover NF04A / NF05A Connector protection; walkway cover As required Optional
Compact 24 VDC UPS NF07A Keeps leak monitoring alive during outages 1 per panel Optional
Control & alarm panel ND01AA Houses controllers, beacon/siren, WCDMA/RS-485/RF comms Per area / zone count Optional

Required items form the minimum working configuration; Optional items are selected to suit site conditions.

How it works

  • On contact with alkali chemicals the nano-carbon layer of NA02AA changes resistance; NB01AA computes the % versus initial resistance and alarms when the lower/upper limit is crossed (default 80% / 130%).
  • Optional colour-changing cover film marks the contact point – technicians can see the leak location on the route.
  • Periodic auto-calibration compensates temperature and humidity; response data is logged for incident tracing.

NCT smart sensor vs. conventional sensors

Criterion NCT smart sensor Conventional sensors
Response time Within 1 second Within 60 seconds
Detection threshold Below 1% 50% or higher (varies by chemical)
Minimum detectable volume Below 0.5 mL 5–10 mL
Sensor durability Excellent electrode corrosion resistance (carbon-based) Prone to corrosion (metal-based)

Source: NCT catalog – NCT Smart Sensor: Proprietary Detection Mechanism.

Typical applications

  • Caustic (NaOH) dosing for pH control, wastewater treatment, gas scrubbers
  • Pulp & paper, textile dyeing, food & beverage CIP using caustic
  • Semiconductor/electronics: alkaline chemical delivery, NH₄OH, H₂O₂
  • Alkali stores, tanks, bunds, pumps, flanges, valves
  • Laboratories, boiler and cooling-tower water treatment dosing

Benefits for contractors & owners

  • Selective response to alkali chemicals, distinguished from water – fewer false alarms in wet areas
  • Responds within 1 second, detects leaks below 0.5 mL (per NCT catalog)
  • Carbon-based materials resist corrosion – outlasts metal-electrode sensors in chemical environments
  • Flexible 370 µm film installs right at leak-prone points: flanges, valves, tank bottoms, drip trays, under lab benches
  • NB01AA: display, adjustable sensitivity, Form C relays, RS-485 Modbus, IoT LoRa
  • S-Mark, CE, KC certified; technical support by DLK

Technical specifications

NA02AA alkali leak sensor cable

Parameter Value
Part number NA02AA (Alkali Sensor – orange)
Type Film-type chemical leak sensor with nano-carbon reactive material
Detectable substances Alkalis: NH₃ (ammonia solution), NaOH, KOH, H₂O₂, etc. (other substances: contact us for model selection)
Dimensions Width 36 mm / Thickness 370 µm
Operating temperature -30 to 100 °C
Material PET
Option Cover film changes colour at the contact point
Sales unit Per metre
Precaution Not standalone – use with NB01AA and NC01AA; replace film after chemical contamination

NB01AA chemical leak sensor controller

Parameter Value
Part number NB01AA
Channels Up to 2 sensors (CH1, CH2)
Dimensions 96 (W) × 66 (H) × 29 (D) mm
Power supply 24 VDC, 200 mA
Communication RS-485 Modbus, 9,600 bps (ID 1–99); IoT LoRa – monitoring and control via mobile app
Relay output 1 Form C × 2 (one relay per channel), 1 A 24 VDC / 0.5 A 125 VAC
Sensor input range 1 kΩ to 5,000 kΩ
Display / setup 4-digit FND display, STATUS / POWER / ALARM1 / ALARM2 LEDs, 4 setup keys; alarm thresholds & auto-calibration as % of initial resistance (default 80% / 130%)
Data Real-time value on site, sensor response data logging
Operating temperature -30 to 100 °C
Housing material PP
Certifications S-Mark, CE, KC

NB02AA master controller

Parameter Value
Part number NB02AA
Function Centrally manages up to 30 NB01AA controllers in parallel on RS-485
Dimensions 108 (W) × 112 (H) × 35 (D) mm
Power supply 24 VDC, 200 mA
Communication RS-485 Modbus, 9,600 bps
Relay output 1 Form C, 1 A 24 VDC / 0.5 A 125 VAC
Operating temperature -30 to 100 °C
Housing material Aluminium (AL)

Sensor connectors

Code Type Dimensions Notes
NC01AA Chemical sensor connector (NA01AA/NA02AA/NA03AA) 55.5 × 18 × 12.6 mm Single type (no START/END); each connector cable is wired to NB01AA
NC02AA Link (corner) connector 75 × 75 × 12.6 mm For corners/bends; compatible with leak and chemical sensors
NC06A Flexible link connector 55.5 × 18 × 12.6 mm × 2 Adjustable intermediate cable – crosses columns, beams, gaps; compatible with leak and chemical sensors

Material PVC, operating temperature -30 to 100 °C.

Protective accessories & backup power (optional)

Code Name Material Dimensions / data Purpose
NF02A / NF02B / NF02C Sensor protective case (PVC) PVC 115 × (200–500 / 501–1,000 / 1,001–2,000) × 50 mm For areas where metal cannot be used – especially highly corrosive chemical areas
NF01A / NF01B / NF01C Sensor protective case (SUS) SUS (inox) 115 × (200–500 / 501–1,000 / 1,001–2,000) × 50 mm Film installed inside; liquid entering through the bottom is detected – mechanical, dirt and outdoor protection
NF04A Connector protective case SUS 70 × 80 × 50 mm Protects connectors from environmental factors and impact
NF05A Sensor protective cover SUS 40 × 15 × 2,400 mm, 1.2 mm thick Cover over the film, fixed with saddles; label on top – for walkways and trolley areas
NF07A UPS – compact 24 VDC model — 84 × 72 × 42 mm; 14.4 V × 3,000 mAh; I/O 24 V (±10%); 400 g Panel-mounted 24 VDC backup for controllers (KC, CE)
NF06A UPS – standard model — 101 × 279 × 142 mm; 12 V / 7 Ah; I/O 220 VAC (±10%, 50/60 Hz); 4.2 kg Keeps the alarm system running during outages (KC, CE)

Wiring & system integration

BMS / SCADA / DCS integration

Method NB01AA output To system Notes
Relay contacts 2 × 1 Form C relays (NO/NC/COM), one per channel; 1 A 24 VDC / 0.5 A 125 VAC DDC/PLC DI, beacon/siren, pump trip / valve interlock Dry contacts – direct wiring
RS-485 Modbus RS-485 Modbus, 9,600 bps, ID 1–99 (parameter P-01) BMS/SCADA/DCS via Modbus gateway; read status and resistance/% values (U-01, U-05) Multi-drop bus; up to 30 units managed by NB02AA master
IoT LoRa LoRa network Mobile app – remote monitoring & alerts Ideal for unmanned warehouses and remote areas
Quick setup: P-01 = Modbus address; P-02 = number of sensors (1 or 2); P-10/P-11 = lower/upper alarm limits (% of initial resistance, default 80%/130%); P-12/P-13/P-14 = auto-calibration; recommended display U-05. Detailed Modbus register map: supplied by DLK per project.

Installation & operation notes

  • Confirm the chemical before choosing the part: NA01AA for acids, NA02AA for alkalis; areas with both need separate routes/channels.
  • Place film at the lowest point of the bund, in drip trays under pumps/valves/flanges, along pipe trenches; use PVC case NF02 in highly corrosive areas.
  • Insert film into NC01AA with the electrode between cover and sensing film, check the rubber seal at the connector base, tighten the cover screws.
  • Wire to NB01AA, apply 24 VDC; set P-01 (Modbus ID), P-02 (sensor count), P-10…P-14 (limits & auto-calibration), display U-05.
  • On alarm: identify channel (ALARM1/ALARM2) → P-02 = 0000 → replace film → P-02 = 0001/0002 → P-03 = 0001 to reset.

Quantity take-off example

Example: alkali chemical station with 4 zones (tank bund 2 × 10 m, pump skid 6 m, pipe route 15 m) – 2 NB01AA on one RS-485 bus

Item Quantity
NA02AA 41 m
NB01AA 2 units
NC01AA 8 pcs
NF02A–C (PVC) Per section in corrosive areas
SMPS 24 VDC ≥ 1 A 1 unit
Signals to DCS/BMS 4 relay contacts + RS-485 Modbus (ID 1, 2)

Frequently asked questions (FAQ)

Which chemicals does NA02AA detect?

NaOH, KOH, NH₃ (ammonia solution), H₂O₂… NCT's chemical range also covers organic solvents; for other chemicals contact DLK for model selection and testing.

What if an area has both acids and alkalis?

Use NA02AA for the alkali route and NA01AA (acid) for the other; one NB01AA accepts 2 sensors, so each type can use its own channel.

Will it alarm on a wet floor?

No – NCT's selective material distinguishes water from chemicals, suitable for wash-down areas and humid cleanrooms.

How are signals sent to BMS/DCS?

Each channel has a Form C relay (dry contact) and all data is available via RS-485 Modbus at 9,600 bps; use NB02AA to manage up to 30 units centrally.

Can the cable be reused after a leak?

The contaminated film section must be replaced; connectors and controller remain, then reset per the procedure.

DLK Trading Service Company Limited is NCT's (Nano Composite Technology, Korea) authorized strategic partner in Vietnam. DLK supplies 100% new genuine products with full import documents, and supports contractors and factories with system sizing and BOQ take-off from drawings, wiring, commissioning and signal integration into BMS / SCADA / DCS.
Need a quotation from drawings / BOQ? Send DLK your layout and the list of zones to monitor – DLK engineers will propose the configuration, take off quantities and provide a BMS wiring diagram. Hotline: +84 93 279 2697 – Sales: +84 70 357 0101.

Data sources: NCT catalog, NCT Leak Sensor Manual, NCT All Conductive Liquid Sensor Manual, nctech.co.kr. Specifications may change with product revisions – please confirm with DLK before ordering.

Mã SP:

Quy cách:

Tình trạng:

Price:

Số lượng

0703570101